AMERICAN Ductile Iron Specials Mechanical Joint Wall Sleeves
MJ Wall Sleeve |
|
MJ and PE Wall Sleeve |
| |
|
|
*T1 for:
4"-24" = .38
30"-36" = 1.00 42"-48" = 1.25 |
|
Increments of sleeve lengths available: 4"-24" = 1" 30"-54" = 2" |
ADIP Table No. 7-1
Size
in. |
Rating
psi |
T
Wall
Thickness
in. |
C
Collar
Diameter
in. |
Collar
Weight
lb |
MJ Wall Sleeve |
MJ & PE Wall Sleeve |
Weight
per 1"
Increment
of Length+
lb |
Lengths
Min.-Max.
in. |
Weight
of 12" lg.
Sleeve
lb |
Lengths
Min.-Max.
in. |
Weight
of 12" lg.
Sleeve
lb |
| 4 |
350 |
0.34 |
11.60 |
6 |
8"-20" |
26 |
8"-20" |
20 |
0.7 |
| 6 |
350 |
0.36 |
13.70 |
7 |
8"-20" |
40 |
8"-20" |
30 |
1.1 |
| 8 |
350 |
0.38 |
15.90 |
9 |
8"-30" |
55 |
8"-30" |
42 |
1.8 |
| 10 |
350 |
0.40 |
18.00 |
10 |
8"-30" |
72 |
8"-30" |
58 |
2.9 |
| 12 |
350 |
0.42 |
20.10 |
11 |
8"-30" |
87 |
8"-30" |
76 |
4.5 |
| 14 |
350 |
0.47 |
22.80 |
13 |
8"-34" |
138 |
8"-36" |
107 |
5.3 |
| 16 |
350 |
0.50 |
24.90 |
14 |
8"-34" |
159 |
8"-36" |
131 |
7.3 |
| 18 |
350 |
0.54 |
27.10 |
16 |
8"-34" |
196 |
8"-36" |
159 |
8.8 |
| 20 |
350 |
0.57 |
29.30 |
17 |
8"-34" |
242 |
8"-36" |
190 |
10.0 |
| 24 |
350 |
0.61 |
34.80 |
21 |
8"-34" |
316 |
8"-36" |
248 |
13.3 |
| 30 |
250 |
1.03 |
39.00 |
73 |
10"-24" |
620 |
10"-24" |
510 |
28.3 |
| 36 |
250 |
1.15 |
45.75 |
87 |
10"-24" |
835 |
10"-24" |
690 |
37.8 |
| 42 |
250 |
1.28 |
53.00 |
149 |
10"-24" |
1115 |
10"-24" |
920 |
48.6 |
| 48 |
250 |
1.42 |
59.75 |
170 |
10"-24" |
1370 |
10"-24" |
1140 |
61.5 |
| **54 |
250 |
1.55 |
65.50 |
184 |
12"-24" |
1375 |
12"-24" |
1225 |
73.9 |
Notes:
Sleeves may be furnished as castings or fabrications, at Foundry option.
*This thickness and other dimensions and weights, etc., will vary slightly because of manufacturing process. Collars welded on fabricated wall sleeves will be steel.
**The 54" Mechanical Joint Wall Sleeve is special with special mechanical joint (gland weight: 360 lbs each; gasket weight: 7 lbs each; 36-1 1/4" X 6" stud bolts each with one hex nut and weighing 3.4 lbs each). Consult AMERICAN for additional information on this special sleeve and for information on 60" & 64" wall sleeves.
Some sizes of wall sleeves in shorter lengths than shown can be furnished by special pattern adaption. Check AMERICAN if required.
+This "Weight per 1" Increment of Length" is the weight to add to -- or subtract from -- the weight of the 12"-long wall sleeve for each 1" variation in sleeve length from 12".
Sleeves will be furnished tapped for studs. Wall collar will be furnished approximately in center unless otherwise specified. Minimum distance from the sleeve end to the center of the collar is 4" for 4"-24" sizes, 5" for 30"-60". For sizes 4"-24", wall collar can be positioned on sleeve in 1" increments; for sizes 30"-54" in 2" increments.
Overall lengths are subject to manufacturing tolerances. If maximum overall length is critical, such as for installation of item inside steel forms, this must be specified on order.
See General Notes.
AMERICAN Ductile Iron Specials Plain End Spool and Integrally Cast Wall Collar Weights Statically Cast Wall Castings

ADIP Table No. 7-3
Size
in. |
Plain End Spools |
Wall Collars |
| Ductile Iron Statically Cast |
Integrally Cast |
| AWWA C100* Class B |
AWWA C100* Class D |
T1
Thickness
in. |
C
Diameter
in. |
Weight
lb |
T
Thickness
in. |
Weight
lb/ft |
T
Thickness
in. |
Weight
lb/ft |
| 30 |
1.03 |
312.7 |
1.37 |
421.3 |
1 |
36.5 |
70 |
| 36 |
1.15 |
418.8 |
1.58 |
582 |
1 |
43 |
88 |
| 42 |
1.28 |
542.3 |
1.78 |
764.2 |
1.25 |
49.5 |
130 |
| 48 |
1.42 |
687.3 |
1.96 |
961 |
1.25 |
56.5 |
172 |
| 54 |
1.55 |
851 |
2.23 |
1226.5 |
1.5 |
63 |
201 |
| 60 |
1.1 |
652.4 |
- |
- |
1.5 |
70.25 |
345 |
| 64 |
1.16 |
733.5 |
- |
- |
1.5 |
74.88 |
395 |
Notes:
*See Section 12, Table No. 12-1 for the obsolete AWWA C100 class thicknesses.
For weight of the 8" length of 4"-48" plain end on fitting per AWWA C110 gauged for MJ, see Section 5, Table No. 5-2.
AMERICAN Ductile Iron Specials Wall Casting Lengths - Statically Cast** Maximum Laying and Overall Lengths
ADIP Table No. 7-6
Type
Joints |
Size
in. |
Maximum Statically Cast Lengths |
Laying Lengths
ft.-in. |
Overall Lengths
ft.-in. |
SKT Depth |
| MJ-W/C-MJ |
30"-36" |
5'-0" |
5'-8" |
4 |
| MJ-W/C-MJ |
42"-48" |
6'-0" |
6'-8" |
4 |
| Fastite-W/C- Fastite |
30"-36" |
5'-0" |
5'-10 1/2 " |
5.25 |
| Fastite-W/C- Fastite |
42" |
5'-6" |
6'-8" |
7.5 |
| Fastite-W/C- Fastite |
48" |
5'-6" |
6'-10" |
8 |
| Fastite-W/C- Fastite |
54" |
5'-6" |
6'-11" |
8.5 |
| Fastite-W/C- Fastite |
60" |
5'-6" |
6'-11 1/2" |
8.75 |
| Fastite-W/C- Fastite |
64" |
5'-6" |
7'-0" |
9 |
| Flange-W/C-Flange |
30"-36" |
5'-6" |
5'-6" |
- |
| Flange-W/C-Flange |
42"- 64" |
6'-0" |
6'-0" |
- |
| MJ-W/C-Flange &MJ-W/C-Plain End |
30"- 36" |
5'-0" |
5'-4" |
4 |
| MJ-W/C-Flange &MJ-W/C-Plain End |
42"-48" |
6'-0" |
6'-4" |
4 |
| Fastite-W/C-Flange |
30"-36" |
5'-0" |
5'-5 1/4" |
5.25 |
| Fastite-W/C-Flange |
42" |
6'-0" |
6'-7 1/2" |
7.5 |
| Fastite-W/C-Flange |
48" |
6'-0" |
6'-8" |
8 |
| Fastite-W/C-Flange |
54" |
6'-0" |
6'-8 1/2" |
8.5 |
| Fastite-W/C-Flange |
60" |
6'-0" |
6'-8 3/4" |
8.75 |
| Fastite-W/C-Flange |
64" |
6'-0" |
6'-9" |
9 |
| Flex Ring-W/C-Flex Ring |
30"-36" |
4'-6" |
6'-0 3/4" |
9.38 |
| Flex Ring-W/C-Flex Ring |
42" |
4'-6" |
6'-3 5/8" |
10.84 |
| Flex Ring-W/C-Flex Ring |
48" |
4'-6" |
6'-6 3/4" |
12.37 |
| Lok Ring-W/C-Lok Ring |
54" |
4'-6" |
6'-2 1/4" |
10.07 |
| Lok Ring-W/C-Lok Ring |
60"-64" |
4'-6" |
6'-3 1/4" |
10.57 |
| Lok Ring-W/C-Flange |
54" |
5'-6" |
6'-4 1/8" |
10.07 |
| Lok Ring-W/C-Flange |
60"-64" |
5'-6" |
6'-4 1/2" |
10.57 |
Notes:
All lengths of Plain End-Thrust Collar-Plain End Wall Pipe are fabricated from centrifugally cast ductile iron pipe.
For minimum lengths see Table No. 7-7 (below).
To determine weight of any wall casting not listed in Table No. 7-8 (below), use data in Table No. 7-3 (above).
Fastite-W/C-Fastite Wall Castings are only available as static castings. All other combinations of joints can be fabricated from centrifugally cast ductile iron pipe with thrust collars as required. See Table No. 7-5.
Correctly installed flanged wall pipe will normally have the bolt holes straddling the horizontal and vertical center lines. Checking with a spirit level or plumb line prior to pouring the walls is recommended.
"W/C" in the description of wall castings refers to wall collar. Wall collar dimensions are shown in Table No. 7-3 (above).
**Most wall pipes will be furnished fabricated from centrifugally cast ductile iron pipe. The statically cast lengths shown in this table may not be readily available.
AMERICAN Ductile Iron Specials Wall Castings - Statically Cast** Minimum Overall Lengths

ADIP Table No. 7-7
Size
in. |
Minimum Overall Lengths in Inches |
MJ-
W/C-
MJ+ |
Fst-
W/C-
Fst |
Flg-
W/C-
Flg |
MJ-
W/C-
Flg* |
Fst-
W/C-
Flg* |
MJ-
W/C-
PE* |
FR-***
W/C-
FR |
LKR-***
W/C-
LKR |
LKR-***
W/C-
Flg |
| 30 |
17 |
20 |
14 |
17 |
20 |
17 |
26 |
- |
- |
| 36 |
17 |
20 |
14 |
17 |
20 |
17 |
26 |
- |
- |
| 42 |
17 |
27 |
15 |
17 |
20 |
17 |
29 |
28 |
21 |
| 48 |
17 |
27 |
15 |
17 |
20 |
17 |
- |
28 |
22 |
| 54 |
- |
27 |
16 |
- |
21 |
- |
- |
26 |
23 |
| 60 |
- |
28 |
18 |
- |
23 |
- |
- |
27 |
23 |
| 64 |
- |
28 |
20 |
- |
23 |
- |
- |
28 |
23 |
Notes:
*Minimum overall lengths for castings with one MJ bell or one Fastite bell are based on the wall collar being located in the center of the overall length. Where the wall collar can be located off-center, away from the socket, some reduction can generally be made in the minimum length.
**Most wall pipes will be furnished fabricated from centrifugally cast ductile iron pipe. The statically cast lengths shown in this table may not be readily available.
***Flex-Ring and Lok-Ring Wall Castings are not illustrated.
Overall lengths are subject to manufacturing tolerances. If maximum overall length is critical, such as for installation of item inside steel forms, this must be specified on order.
Some sizes of wall pipe in shorter lengths than shown can be furnished by special pattern adaptation. Check AMERICAN if required.
"W/C" in the description of wall castings refers to wall collar. Wall collar dimensions are shown in Table No. 7-3 (above).
Correctly installed flanged wall pipe will normally have the bolt holes straddling the horizontal and vertical centerlines. Checking with a spirit level or plumb line prior to pouring the walls is recommended.
+Mechanical joint end wall sleeves are available in some sizes with shorter lengths than statically cast wall pipe per this table (see Table 7-1 above).
|